backflow preventer, type CA

figure 362 2G

  • to protect drinking water against backflow of fluids up to and including category 3 according DIN 1988-100
  • wetted metal parts made from dezincification-free and corrosion-resistant gunmetal, resistant against aggressive water
  • with stainless steel mesh at inlet

Product Features

  • to protect drinking water against backflow of fluids up to and including category 3 according DIN 1988-100
  • wetted metal parts made from dezincification-free and corrosion-resistant gunmetal, resistant against aggressive water
  • with stainless steel mesh at inlet
  • maintenance-free backup cartridge
  • with non-controllable pressure zone
  • male union thread
  • drain connection of plastic and gunmetal according to DIN EN 1717
  • inlet and outlet with check cartridge
  • free from dead spots
  • for horizontal installation, drain valve down
  • maintenance requirements in accordance with DIN EN 806-5 must be complied with

Standards and Approvals

  • DVGW approval
  • KIWA approval
  • BELGAQUA approval
  • plastic parts with KTW and W 270 approval
  • according to accepted materials list from German environmental agency
  • soundproofing certification according to DIN EN ISO 3822 Class 1
  • DIN EN 14367 / EN 1717
  • ÜA-Reg.-Nr. R-15.2.3-21-17048, WIEN-ZERT

Technical data

  • pressure rating PN 10
  • max. operating temperature 60 °C
  • short-term peak temperature 65 °C
figure 362 2G
Part no. DN A1 D1
(mm)
H1
(mm)
L1
(mm)
nominal
connection
diameter, waste water (mm)
kg
3622G01500 15 G 3/4 40 103 79.5 40 0.65
3622G02000 20 G 1 40 103 79.5 40 0.66

CAD models

Part no. DN CAD model
3622G01500 15 Show 3D data
3622G02000 20 Show 3D data

Downloads

Data sheet
File type
Product datasheet
pdf
Instructions
File type
Installation and operating instructions for CA pipe separator
pdf (4.3 MB)
Technical information
File type
Spare Parts List
pdf (4.1 MB)
Flow Diagram backflow preventer type CA